A battery unit not following its dispatch order raises an event

A battery unit idle or moving against its dispatch order for 15 minutes now raises an event on the plant's "Events" page. The event closes only when the unit or the storage as a whole follows an order again, or when its own fault stop, safety alarm or silence takes over.

  • Components behind a down or refusing data logger now appear under that data logger on the plant's "Events" page.
  • An event opens when a component's energy counter disagrees with its power by more than 25 percent.
  • Conflicting values from two or more components of one data logger now raise an event.
  • Turbine and storage silence now join the plant's no-communication summary instead of its outage summary.